IP00 · open frame, for cabinet mounting Single-phase 400 V to 24 V transformer, open frame (IP00), connection terminals on the front

Single-phase transformer 400 V / 24 V

24 V AC from two phases · 63 VA to 20 kVA · IP00, IP23 or IP54 · made in France

5.0 · 1 review

63 VA2.62 A at 24 V

  • —
  • —
  • 2-year warranty · wound and tested in Gailhan

Key features

This single-phase 400 V to 24 V transformer connects between two phases of a 400 V supply — formerly 380 V — and delivers 24 volts AC: the voltage of control circuits in control panels without a neutral (contactor and relay coils, indicator lamps, solenoid valves), as well as low-voltage lighting and automation. The primary and secondary are two separate windings. From 63 VA to 20 kVA, open frame (IP00), with a ventilated cover (IP23) or in a sealed housing (IP54): it is wound and tested in our workshop in Gailhan, in the Gard (southern France).

Your supply400 V ~between two phases, no neutral
Transformer400 → 24 Visolates and steps down
Your circuits24 V ~AC: control, relays, solenoid valves
24 V ACThe voltage for control circuits, relays and solenoid valves.
Between two phasesIt connects to two phases of the 400 V supply: no neutral is needed.
Two separate windingsNo electrical connection between the 400 V and the 24 V.
Screw terminals up to 55 A, lugs aboveScrew terminals up to 1 kVA on this model, lugs above that. Terminal marking: 1 and 2 on the primary (0 and 400 V), 3 and 4 on the secondary (0 and 24 V), earth on the primary side.
Open frame, covered or sealedIP00 for cabinet mounting, IP23 with a ventilated cover, IP54 in a moulded housing or a sealed enclosure.
Made and tested in GailhanWound, wired and 100 % tested in our workshop in the Gard, southern France, before dispatch.
No neutral? That is exactly what it is for

The primary connects between two phases of the 400 V supply (L1 and L2, for example): it needs neither a neutral nor a 230 V supply. If your panel has a neutral, the 230 V / 24 V transformer is also suitable.

24 V AC, not DC

It supplies 24 V AC (marked 24 V AC or 24 V ~). A PLC, a sensor or electronics running on 24 V DC need a power supply: see AC or DC.

Protect both phases

On the primary, both phases go through a two-pole type D circuit breaker or two aM fuses: 2 A for the 63 VA, 4 A for the 1,000 VA. On the secondary, protection rated for the 24 V current: the rating for each size is given in the table.

When should you use a 400 V to 24 V transformer?

  • Control circuits in control panels: 24 V AC contactor and relay coils.
  • Indicator lamps, illuminated push buttons and industrial panel signalling.
  • 24 V AC solenoid valves and motorised valves.
  • Automation systems and motor drives supplied from a 400 V supply without a neutral.
  • 24 V low-voltage lighting, machine lamps.
  • Test benches and machines that need an AC extra-low voltage.

It works on 50 and 60 Hz supplies and delivers AC: for 24 V DC, see the next section.

24 V AC or 24 V DC?

Check the rating plate on your device. The marking tells you which product you need.

24 V AC, 24 VAC or 24 V ~ → this transformer24 V DC, 24 VDC or 24 V ⎓ → a power supply
24 V alternating current · AC · ~This transformer
  • Small 24 V AC motors and automation systems
  • 24 V AC solenoid valves and motorised valves
  • 24 V AC relay and contactor coils
  • Machine lamps and 24 V lighting
  • 24 V AC indicator lamps and signalling
  • Indicator lights marked 24 V AC
Choose your rating

Specifications of the 400 V / 24 V transformer

Values for the selected configuration: 63 VA · IP00.

Rating63 VA50 / 60 Hz
Primary400 V ~0.16 A
Secondary24 V ~2.62 A
ProtectionIP00Open frame, for cabinet mounting
Primary
Voltage
400 V AC, between two phases (formerly 380 V)
Rated current
—
Terminals
1 (0 V) · 2 (400 V) · earth
Recommended protection
—
Secondary
On-load voltage
24 V AC
No-load voltage
—
Rated current
—
Terminals
3 (0 V) · 4 (24 V)
Recommended protection
—
Construction
Type
Dry-type transformer, two separate windings
Core
EI laminations, flux density 1.2 T
Insulation class
H (180 °C)
Temperature rise
50 °C, 40 °C maximum ambient
Standards
EN 61558-2-4 and EN 61558-2-6
Thermal protection
On request
Enclosure
IP rating
—
Overall dimensions L × W × H
—
Weight
—
Mounting
—
Altitude
3,000 m maximum
Connection
Screw terminals up to 55 A (1 kVA on this model), lugs above
Performancedesign values
Full-load efficiency—
No-load losses—
Load losses—
Full-load voltage drop—

Ratings and prices

From 63 VA to 20 kVA. Above that, or for another voltage, on request.

W × 1.25 = 250 VA → recommended 250 VA
Rating24 V currentPrimary fuse24 V protectionNo-load / load lossesEfficiencyWeightDimensions (mm)Price ex VAT
63 VA2.6 AaM 2 AaM 4 A2 / 3.5 W90.5 %1.5 kg75 × 68 × 73€47.42
100 VA4.2 AaM 2 AaM 6 A3 / 5.2 W92.0 %2 kg84 × 82 × 78€57.42
160 VA6.7 AaM 2 AaM 8 A4 / 8.6 W91.9 %2.5 kg96 × 89 × 87€63.25
200 VA8.3 AaM 2 AaM 10 A5 / 8.9 W93.0 %2.6 kg118 × 97 × 97€66.58
250 VA10.4 AaM 2 AaM 12 A6 / 10.1 W93.6 %3.9 kg108 × 95 × 100€78.25
300 VA12.5 AaM 2 AaM 16 A6 / 14.6 W93.0 %4 kg108 × 103 × 94€80.75
400 VA16.7 AaM 2 AaM 20 A8 / 15 W94.2 %6 kg126 × 122 × 108€102.42
500 VA20.8 AaM 2 AaM 25 A10 / 18.6 W94.2 %6.8 kg126 × 110 × 115€112.42
630 VA26.2 AaM 2 AaM 32 A12 / 22.7 W94.4 %9 kg150 × 124 × 126€132.42
750 VA31.2 AaM 2 AaM 40 A15 / 24.4 W94.8 %10.3 kg150 × 120 × 135€144.92
1 kVA41.7 AaM 4 AaM 50 A18 / 29.2 W95.3 %14 kg150 × 144 × 127€175.75
1.6 kVA66.7 AaM 6 AaM 80 A19 / 46.1 W95.9 %16.4 kg180 × 140 × 160€219.92
2 kVA83.3 AaM 6 AaM 100 A19 / 59.5 W96.1 %20 kg180 × 160 × 160€243.25
2.5 kVA104.2 AaM 8 AaM 125 A24 / 66.7 W96.4 %24 kg180 × 180 × 150€250.75
3 kVA125.0 AaM 8 AaM 160 A37 / 82.2 W96.0 %29 kg180 × 200 × 160€288.25
4 kVA166.7 AaM 12 AaM 200 A42 / 105.2 W96.3 %33 kg240 × 190 × 220€425.75
5 kVA208.3 AaM 16 AaM 250 A45 / 129.7 W96.5 %36 kg240 × 200 × 220€458.25
6.3 kVA262.5 AaM 20 AaM 315 A56 / 132.3 W97.0 %40 kg240 × 210 × 220€483.25
7.5 kVA312.5 AaM 20 AaM 400 A56 / 152.6 W97.2 %46 kg240 × 230 × 220€548.25
10 kVA416.7 AaM 32 AaM 500 A—*—*75 kg390 × 150 × 470€1,012.42
15 kVA625.0 AaM 40 AaM 800 A—*—*80 kg390 × 160 × 470€1,145.75
20 kVA833.3 AaM 63 AaM 1000 A—*—*95 kg390 × 170 × 470€1,279.92

aM fuses sized for the rated current; alternatively, a type D circuit breaker of the same rating. * 10 to 20 kVA: catalogue weights and dimensions, losses on request.

Cable size on the 24 V side

Voltage drop depends on the current and the length. Aim for less than 5 % (3 % for lighting).

A
m
The calculation allows for both the outgoing and return conductors.
Application
Recommended cable size——
Cable sizeDropVoltage at the deviceDrop (%)Verdict

Copper cable, resistivity 0.0225 Ω·mm²/m (at operating temperature), outgoing and return conductors, reactance ignored. “Too small for this current”: current-carrying capacity of a PVC-insulated copper cable in conduit, two loaded conductors, for guidance only. Final sizing is the installer's responsibility (IEC 60364; NF C 15-100 in France).

Connection and dimensions

Extracts from the datasheet: diagram, terminal block and dimensions.

Connection diagram
PRIMARYSECONDARYMagnetic corePrimary 1 · 400 V10 V2400 VSecondary 1 · 24 V · 63 VA30 V424 V
P10 V1400 V2S10 V324 V4
Dimensioned drawing
Technical document for the TMN40024 series
PDF · specifications, ratings and part numbers, protection
FRENDEESIT

Primary protection

—

—

24 V protection

—

As close as possible to the transformer, on the 24 V outgoing circuit.

Safety

  • Connection with the power off, by a qualified person.
  • Earth connected before switching on.
  • IP00: inside a closed cabinet or enclosure.

Standards, warranty and options

A standard transformer, made in Gailhan and also available in other voltages.

EN 61558-2-4 and -2-6with Part 1: isolation and safety (SELV)
CE markingLow Voltage, EMC
RoHSfree of lead and restricted substances
2-year warrantyon this transformer
Made in FranceGailhan workshop (Gard, southern France)
Parcel or palletpallet over 30 kg

Frequently asked questions

About the 400 V / 24 V single-phase transformer, connected between two phases.

How do I connect a 400 V to 24 V transformer?

The primary connects between two phases of the 400 V supply, on terminals 1 and 2, with earth to the primary earth terminal; the 24 V circuits are fed from terminals 3 (0 V) and 4 (24 V). The connection diagram is on the datasheet.

Does this 400 V to 24 V transformer need a neutral?

No: it connects between two phases. It is the 400 V to 24 V control transformer for panels that have no neutral. If a neutral is available, a 230 V / 24 V transformer will also do the job.

380 V or 400 V: is it the same transformer?

Yes: 380 V is the former name for the 400 V supply. A 380 V to 24 V transformer and a 400 V to 24 V transformer are the same unit.

Does this 400 V to 24 V transformer supply DC?

No: it supplies 24 V AC. For 24 V DC (PLCs, sensors, electronics), you need a power supply: a regulated 24 V power supply or a rectified 24 V power supply.

Which rating should I choose?

Add up the power of the coils, indicator lamps and equipment supplied at 24 V, multiply by 1.25 and take the next rating up: 100 W of control circuits needs 125 VA, so a 160 VA transformer. The calculator above the table does this for you.

Why do I measure more than 24 V?

Off load, the voltage is slightly higher: about 25.4 V on the 63 VA and 24.7 V on the 1,000 VA. It falls to 24 V when the transformer delivers its rated current. Measure with your multimeter set to AC (V~).

What protection should I install?

On the primary, a two-pole type D circuit breaker or two aM fuses rated for the primary current: 2 A for the 63 VA, 4 A for the 1,000 VA. On the secondary, protection rated for the 24 V current: a 4 A aM fuse for the 63 VA, 50 A for the 1,000 VA. At switch-on, the transformer draws about twelve times its rated current.

What cable size on the 24 V side?

It depends on the current and the length: at 24 V, a 1 V drop is already 4 %. The cable size calculator works it out for your circuit.

IP00, IP23 or IP54: which should I choose?

IP00: open-frame transformer, to be installed in a cabinet or enclosure. IP23: ventilated cover, for a dry room. IP54: moulded housing up to 630 VA, sealed enclosure above that, protected against dust and splashing water. All about IP ratings.

Is it a safety isolating transformer (SELV)?

Yes: 24 V AC is an extra-low voltage, and this transformer complies with the current standards, EN 61558-2-4 and EN 61558-2-6 (safety isolating transformers).