IP00 · open frame, for cabinet mounting 400 V to 230 V single-phase transformer, open frame (IP00), connection terminals on the front

Single-phase transformer 400 V / 230 V

230 V from two phases, no neutral needed · 63 VA to 20 kVA · IP00, IP23 or IP54 · made in France

5.0 · 4 reviews

63 VA0.27 A at 230 V

  • —
  • —
  • 2-year warranty · wound and tested in Gailhan

Key features

This 400 V to 230 V single-phase transformer connects between two phases of a 400 V supply — formerly 380 V — and delivers single-phase 230 V, isolated from the supply: enough to power 230 V equipment where there is no neutral, or to separate it galvanically from the installation. The primary and secondary are two separate windings. From 63 VA to 20 kVA, open frame (IP00), with a ventilated cover (IP23) or in a sealed housing (IP54): it is wound and tested in our workshop in Gailhan, in the Gard (southern France).

Your supply400 V ~between two phases, no neutral
Transformer400 → 230 Vsteps down and isolates
Your equipment230 V ~single-phase, separated from the supply
230 V without a neutralIt connects to two phases of the 400 V supply and delivers single-phase 230 V.
Galvanic isolationThe 230 V output has no electrical connection with the 400 V supply.
Earth-referenced neutral if neededA secondary terminal connected to earth becomes a neutral.
Screw terminals up to 55 A, lugs aboveScrew terminals up to 10 kVA on this model, lugs above that. Terminal marking: 1 and 2 on the primary (0 and 400 V), 3 and 4 on the secondary (0 and 230 V), earth on the primary side.
Electrostatic shield as standardConnected to earth, it limits the transfer of disturbances between primary and secondary.
Made and tested in GailhanWound, wired and 100 % tested in our workshop in the Gard, southern France, before dispatch.
Three-phase to single-phase: which should I choose?

This transformer takes two of the three phases: for a few hundred VA or a few kVA, it is the simplest solution. Beyond that, to avoid unbalancing the supply, choose the three-phase to single-phase transformer, which spreads the load over all three phases.

Off load, slightly more than 230 V

That is normal: about 244 V off load on the 63 VA, 237 V on the 1,000 VA. The voltage comes back to 230 V when the transformer delivers its rated current.

Protect both phases

On the primary, both phases go through a two-pole type D circuit breaker or two aM fuses: 2 A for the 63 VA, 4 A for the 1,000 VA; for the 2.5 kVA, 8 A aM fuses or a 10 A type D circuit breaker. The rating for each size is given in the table.

When should you use a 400 V to 230 V single-phase transformer?

  • Supplying 230 V equipment from a 400 V supply without a neutral: heat pump, pump, tools, lighting.
  • Industrial switchboards and panels on 3 × 400 V without a neutral that need to provide a few 230 V sockets.
  • Galvanically separating 230 V equipment from the supply that feeds it.
  • Recreating an earthed neutral for a single-phase appliance.
  • Older systems at 380 V between phases, during refurbishment.
  • Test benches and workshops supplied at 400 V.

It works on 50 and 60 Hz supplies. For high power on a three-phase supply, see the three-phase to single-phase transformer.

Specifications of the 400 V / 230 V single-phase transformer

Values for the selected configuration: 63 VA · IP00.

Rating63 VA50 / 60 Hz
Primary400 V ~0.16 A
Secondary230 V ~0.27 A
ProtectionIP00Open frame, for cabinet mounting
Primary
Voltage
400 V AC, between two phases (formerly 380 V)
Rated current
—
Terminals
1 (0 V) · 2 (400 V) · earth
Recommended protection
—
Secondary
On-load voltage
230 V AC
No-load voltage
—
Rated current
—
Terminals
3 (0 V) · 4 (230 V)
Recommended protection
—
Construction
Type
Dry-type transformer, two separate windings
Core
EI laminations, flux density 1.2 T
Insulation class
H (180 °C)
Temperature rise
50 °C, 40 °C maximum ambient
Standards
EN 61558-2-4 (isolating transformers)
Electrostatic shield
Fitted as standard, earthed
Thermal protection
On request
Enclosure
IP rating
—
Overall dimensions L × W × H
—
Weight
—
Mounting
—
Altitude
3,000 m maximum
Connection
Screw terminals up to 55 A (10 kVA on this model), lugs above
Performancedesign values
Full-load efficiency—
No-load losses—
Load losses—
Full-load voltage drop—

Ratings and prices

From 63 VA to 20 kVA. Above that, or for another voltage, on request.

W × 1.25 = 250 VA → recommended 250 VA
Rating230 V currentPrimary fuse230 V protectionNo-load / load lossesEfficiencyWeightDimensions (mm)Price ex VAT
63 VA0.3 AaM 2 AaM 2 A2 / 3.6 W90.5 %1.5 kg75 × 68 × 73€47.42
100 VA0.4 AaM 2 AaM 2 A3 / 5 W92.0 %2 kg84 × 82 × 78€57.42
160 VA0.7 AaM 2 AaM 2 A4 / 8.5 W92.5 %2.5 kg96 × 89 × 87€63.25
200 VA0.9 AaM 2 AaM 2 A5 / 8.8 W93.0 %2.6 kg118 × 97 × 97€66.58
250 VA1.1 AaM 2 AaM 2 A5 / 11.9 W93.2 %3.9 kg108 × 95 × 100€78.25
300 VA1.3 AaM 2 AaM 2 A6 / 14.6 W93.0 %4 kg108 × 103 × 94€80.75
400 VA1.7 AaM 2 AaM 2 A8 / 15.1 W94.2 %6 kg126 × 122 × 108€102.42
500 VA2.2 AaM 2 AaM 4 A9 / 15.2 W95.2 %6.8 kg126 × 110 × 115€112.42
630 VA2.7 AaM 2 AaM 4 A12 / 22.4 W94.6 %9 kg150 × 124 × 126€132.42
750 VA3.3 AaM 2 AaM 4 A15 / 24.3 W94.8 %10.3 kg150 × 120 × 135€144.92
1 kVA4.3 AaM 4 AaM 6 A18 / 28.4 W95.4 %14 kg150 × 144 × 127€175.75
1.6 kVA7.0 AaM 6 AaM 8 A19 / 46.4 W95.9 %16.4 kg180 × 140 × 160€219.92
2 kVA8.7 AaM 6 AaM 10 A19 / 58.6 W96.1 %20 kg180 × 160 × 160€243.25
2.5 kVA10.9 AaM 8 AaM 12 A24 / 66.6 W96.4 %24 kg180 × 180 × 150€250.75
3 kVA13.0 AaM 8 AaM 16 A29 / 128.3 W94.8 %29 kg180 × 200 × 160€288.25
4 kVA17.4 AaM 12 AaM 20 A42 / 103.5 W96.4 %33 kg240 × 190 × 220€425.75
5 kVA21.7 AaM 16 AaM 25 A45 / 122.1 W96.7 %36 kg240 × 200 × 220€458.25
6.3 kVA27.4 AaM 20 AaM 32 A56 / 129.8 W97.0 %40 kg240 × 210 × 220€483.25
7.5 kVA32.6 AaM 20 AaM 40 A56 / 154.8 W97.2 %46 kg240 × 230 × 220€548.25
10 kVA43.5 AaM 32 AaM 50 A—*—*75 kg390 × 150 × 470€1,012.42
15 kVA65.2 AaM 40 AaM 80 A—*—*80 kg390 × 160 × 470€1,145.75
20 kVA87.0 AaM 63 AaM 100 A—*—*95 kg390 × 170 × 470€1,279.92

aM fuses sized for the rated current; alternatively, a type D circuit breaker of the same rating. * 10 to 20 kVA: catalogue weights and dimensions, losses on request.

Connection and dimensions

Extracts from the datasheet: diagram, terminal block and dimensions.

Connection diagram
PRIMARYSECONDARYMagnetic corePrimary 1 · 400 V10 V2400 VSecondary 1 · 230 V · 63 VA30 V4230 V
P10 V1400 V2S10 V3230 V4
Dimensioned drawing
Technical document for the TMN400230 series
PDF · specifications, ratings and part numbers, protection
FRENDEESIT

Primary protection

—

—

230 V protection

—

As close as possible to the transformer, on the 230 V outgoing circuit.

Safety

  • Connection with the power off, by a qualified person.
  • Earth connected before switching on.
  • IP00: inside a closed cabinet or enclosure.

Standards, warranty and options

A standard transformer, made in Gailhan and also available in other voltages.

EN 61558-2-4with Part 1: isolating transformers
CE markingLow Voltage, EMC
RoHSfree of lead and restricted substances
2-year warrantyon this transformer
Made in FranceGailhan workshop (Gard, southern France)
Parcel or palletpallet over 30 kg
EnclosuresIP23 cover, IP54 moulded housing or enclosure

Frequently asked questions

About the 400 V / 230 V single-phase transformer, connected between two phases.

How do I get 230 V from a 400 V supply without a neutral?

With this single-phase 400 V to 230 V transformer: its primary connects between two phases of the 400 V supply, and its secondary delivers 230 V to the equipment. For high power, the three-phase to single-phase transformer spreads the load over all three phases.

400 V three-phase to 230 V single-phase transformer: is this the product?

This transformer uses two phases of the three-phase supply: it is suitable for a few kVA. For a transformer connected to all three phases, which spreads the load, choose the three-phase to single-phase transformer.

380 V or 400 V: is it the same transformer?

Yes: 380 V and 220 V are the former names for 400 V and 230 V. A 380 V to 220 V transformer and a 400 V to 230 V transformer are the same unit.

Is it an autotransformer?

No: the primary and secondary are two separate windings, with no electrical connection. A 400 V / 230 V autotransformer has only one common winding and does not isolate the equipment from the supply.

Which rating should I choose?

Add up the power of the equipment supplied, multiply by 1.25 and take the next rating up: a 1,500 W heat pump needs 1,875 VA, so a 2 kVA transformer. The calculator above the table does this for you.

How do I connect a 400 V to 230 V transformer?

Two phases of the 400 V supply go to primary terminals 1 and 2, and earth to the earth terminal; the equipment is fed from secondary terminals 3 and 4. Connecting a secondary terminal to earth (earth-referenced neutral) depends on the application: it is the installer's choice.

What protection should I install?

On the primary, a two-pole type D circuit breaker or two aM fuses rated for the primary current: 2 A for the 63 VA, 4 A for the 1,000 VA. On the secondary, the protection of the equipment supplied. At switch-on, the transformer draws about twelve times its rated current.

IP00, IP23 or IP54: which should I choose?

IP00: open-frame transformer, to be installed in a cabinet or enclosure. IP23: ventilated cover, for a dry room. IP54: moulded housing up to 630 VA, sealed enclosure above that, protected against dust and splashing water. All about IP ratings.

Customer reviews

Reviews posted by customers who bought this transformer (in French).

5.0
4 reviews · 4 five-star
Mohamed Chiba · 8 avril 2026

la pompe à chaleur piscine refonctionne et la piscine est chauffée.merci

Eric ROSSERO · 3 octobre 2025

Produit de qualité nous espérons produit en France

63 VA · IP00—