← Single-Phase Transformers
IP00 · open frame, for cabinet mounting 230V to 400V single-phase transformer, open frame (IP00), connection terminals on the front

Single-phase transformer 230 V / 400 V

Single-phase 400 V from a 230 V supply · 63 VA to 20 kVA · IP00, IP23 or IP54 · made in France

5.0 · 1 review

63 VA0.16 A at 400 V

  • —
  • —
  • 2-year warranty · wound and tested in Gailhan

Key features

This 230V to 400V single phase transformer steps the 230 V mains — formerly 220 V — up to 400 volts single-phase AC, isolated from the supply: to power a machine or device designed for 400 V across two wires, where only 230 V is available. It does not create three-phase. The primary and secondary are two separate windings. From 63 VA to 20 kVA, open frame (IP00), with a ventilated cover (IP23) or in a sealed housing (IP54): it is wound and tested in our workshop in Gailhan, in the Gard (southern France).

Your supply230 V ~single-phase, formerly 220 V
Transformer230 → 400 Visolates and steps up
Your equipment400 V ~single-phase, across two wires
Single-phase 400 VFor equipment designed for 400 V across two wires, on a 230 V site.
Two separate windingsNo electrical connection between the 230 V and the 400 V.
Screw terminals up to 55 A, lugs aboveScrew terminals up to 10 kVA on this model, lugs above that. Terminal marking: 1 and 2 on the primary (0 and 230 V), 3 and 4 on the secondary (0 and 400 V), earth on the primary side.
Open frame, covered or sealedIP00 for cabinet mounting, IP23 with a ventilated cover, IP54 in a moulded housing or a sealed enclosure.
Electrostatic shield as standardConnected to earth, it limits the transfer of disturbances between primary and secondary.
Made and tested in GailhanWound, wired and 100 % tested in our workshop in the Gard, southern France, before dispatch.
It does not create three-phase

It delivers 400 V across two wires, single-phase. A three-phase motor or machine needs a phase converter, which this transformer does not replace: tell us about your machine.

The other way round?

From 400 V to single-phase 230 V: the 400 V / 230 V transformer; from a heavily loaded three-phase supply, the three-phase to single-phase transformer.

Off load, you will measure slightly more than 400 V

That is normal: about 424 V off load on the 63 VA, 412 V on the 1,000 VA. The voltage falls to 400 V at full load.

When should you use a 230V to 400V single phase transformer?

  • Single-phase machines and equipment designed for 400 V, on a site that only has 230 V.
  • Replacing a 220 V / 380 V transformer in an existing installation.
  • Test benches and equipment that need 400 V isolated from the mains.

It works on 50 and 60 Hz supplies and delivers single-phase 400 V: it does not produce three-phase.

Specifications of the 230 V / 400 V single-phase transformer

Values for the selected configuration: 63 VA · IP00.

Rating63 VA50 / 60 Hz
Primary230 V ~0.27 A
Secondary400 V ~0.16 A
ProtectionIP00Open frame, for cabinet mounting
Primary
Voltage
230 V AC (formerly 220 V)
Rated current
—
Terminals
1 (0 V) · 2 (230 V) · earth
Recommended protection
—
Secondary
On-load voltage
400 V AC
No-load voltage
—
Rated current
—
Terminals
3 (0 V) · 4 (400 V)
Recommended protection
—
Construction
Type
Dry-type transformer, two separate windings
Core
EI laminations, flux density 1.2 T
Insulation class
H (180 °C)
Temperature rise
50 °C, 40 °C maximum ambient
Standards
EN 61558-2-4 (isolating transformers)
Electrostatic shield
Fitted as standard, earthed
Thermal protection
On request
Enclosure
IP rating
—
Overall dimensions L × W × H
—
Weight
—
Mounting
—
Altitude
3,000 m maximum
Connection
Screw terminals up to 55 A (10 kVA on this model), lugs above
Performancedesign values
Full-load efficiency—
No-load losses—
Load losses—
Full-load voltage drop—

Ratings and prices

From 63 VA to 20 kVA. Above that, or for another voltage, on request.

W × 1.25 = 250 VA → recommended 250 VA
Rating400 V currentPrimary fuse400 V protectionNo-load / load lossesEfficiencyWeightDimensions (mm)Price ex VAT
63 VA0.2 AaM 2 AaM 2 A2 / 3.6 W90.5 %1.5 kg75 × 68 × 73€47.42
100 VA0.2 AaM 2 AaM 2 A3 / 5 W92.0 %2 kg84 × 82 × 78€57.42
160 VA0.4 AaM 2 AaM 2 A4 / 8.5 W92.5 %2.5 kg96 × 89 × 87€63.25
200 VA0.5 AaM 2 AaM 2 A5 / 8.8 W93.0 %2.6 kg118 × 97 × 97€66.58
250 VA0.6 AaM 2 AaM 2 A5 / 11.9 W93.2 %3.9 kg108 × 95 × 100€78.25
300 VA0.8 AaM 2 AaM 2 A6 / 14.6 W93.0 %4 kg108 × 103 × 94€80.75
400 VA1.0 AaM 2 AaM 2 A8 / 15.1 W94.2 %6 kg126 × 122 × 108€102.42
500 VA1.2 AaM 4 AaM 2 A9 / 15.2 W95.2 %6.8 kg126 × 110 × 115€112.42
630 VA1.6 AaM 4 AaM 2 A12 / 22.4 W94.6 %9 kg150 × 124 × 126€132.42
750 VA1.9 AaM 4 AaM 2 A15 / 24.3 W94.8 %10.3 kg150 × 120 × 135€144.92
1 kVA2.5 AaM 6 AaM 4 A18 / 28.4 W95.4 %14 kg150 × 144 × 127€175.75
1.6 kVA4.0 AaM 8 AaM 6 A19 / 46.4 W95.9 %16.4 kg180 × 140 × 160€219.92
2 kVA5.0 AaM 10 AaM 6 A19 / 58.5 W96.1 %20 kg180 × 160 × 160€243.25
2.5 kVA6.2 AaM 12 AaM 8 A24 / 66.8 W96.4 %24 kg180 × 180 × 150€250.75
3 kVA7.5 AaM 16 AaM 8 A29 / 128.2 W94.8 %29 kg180 × 200 × 160€288.25
4 kVA10.0 AaM 20 AaM 12 A42 / 103.3 W96.4 %33 kg240 × 190 × 220€425.75
5 kVA12.5 AaM 25 AaM 16 A45 / 121.2 W96.7 %36 kg240 × 200 × 220€458.25
6.3 kVA15.8 AaM 32 AaM 20 A56 / 130.1 W97.0 %40 kg240 × 210 × 220€483.25
7.5 kVA18.8 AaM 40 AaM 20 A56 / 154.8 W97.2 %46 kg240 × 230 × 220€548.25
10 kVA25.0 AaM 50 AaM 32 A—*—*75 kg390 × 150 × 470€1,012.42
15 kVA37.5 AaM 80 AaM 40 A—*—*80 kg390 × 160 × 470€1,145.75
20 kVA50.0 AaM 100 AaM 63 A—*—*95 kg390 × 170 × 470€1,279.92

aM fuses sized for the rated current; alternatively, a type D circuit breaker of the same rating. * 10 to 20 kVA: catalogue weights and dimensions, losses on request.

Connection and dimensions

Extracts from the datasheet: diagram, terminal block and dimensions.

Connection diagram
PRIMARYSECONDARYMagnetic corePrimary 1 · 230 V10 V2230 VSecondary 1 · 400 V · 63 VA30 V4400 V
P10 V1230 V2S10 V3400 V4
Dimensioned drawing
Technical document for the TMN230400 series
PDF · specifications, ratings and part numbers, protection
FRENDEESIT

Primary protection

—

—

400 V protection

—

As close as possible to the transformer, on the 400 V outgoing circuit.

Safety

  • Connection with the power off, by a qualified person.
  • Earth connected before switching on.
  • IP00: inside a closed cabinet or enclosure.

Standards, warranty and options

A standard transformer, made in Gailhan and also available in other voltages.

EN 61558-2-4with Part 1: isolating transformers
CE markingLow Voltage, EMC
RoHSfree of lead and restricted substances
2-year warrantyon this transformer
Made in FranceGailhan workshop (Gard, southern France)
Parcel or palletpallet over 30 kg
EnclosuresIP23 cover, IP54 moulded housing or enclosure

Frequently asked questions

About the 230 V / 400 V single-phase transformer.

Does this 230V to 400V transformer supply three-phase?

No: it delivers single-phase 400 V, across two wires. A transformer cannot create the three phases: for a three-phase machine, you need a phase converter. Tell us what you need.

220V to 380V or 230V to 400V: what is the difference?

None: 220 V and 380 V are the former names for 230 V and 400 V. A 220V to 380V transformer and a 230V to 400V transformer are the same unit.

Which rating should I choose?

Add up the power of the equipment supplied at 400 V, multiply by 1.25 and take the next rating up: 2,000 W needs 2,500 VA; 4,000 W needs 5,000 VA. For a motor, allow a bigger margin.

Why do I measure more than 400 V?

Off load, the voltage is slightly higher: about 424 V on the 63 VA and 412 V on the 1,000 VA. It falls to 400 V when the transformer delivers its rated current.

How do I connect a 230V to 400V transformer?

The 230 V supply goes to terminals 1 (0 V) and 2 (230 V), and earth to the primary earth terminal; your 400 V equipment is fed from terminals 3 (0 V) and 4 (400 V). The connection diagram is on the datasheet.

What protection should I install?

On the primary, an aM fuse or a type D circuit breaker rated for the primary current: 2 A for the 63 VA, 6 A for the 1,000 VA. On the secondary, protection rated for the 400 V current: a 2 A aM fuse for the 63 VA, 4 A for the 1,000 VA. At switch-on, the transformer draws about twelve times its rated current; the protection rating for each size is given in the table.

And to go from 400 V to 230 V?

That calls for the 400 V / 230 V single-phase transformer, connected between two phases. For high power on a three-phase supply, the three-phase to single-phase transformer spreads the load.

IP00, IP23 or IP54: which should I choose?

IP00: open-frame transformer, to be installed in a cabinet or enclosure. IP23: ventilated cover, for a dry room. IP54: moulded housing up to 630 VA, sealed enclosure above that, protected against dust and splashing water. All about IP ratings.

Customer reviews

Reviews posted by customers who bought this transformer (in French).

5.0
1 review · 1 five-star
Claude Boutonnet · 12 octobre 2021

Transformateur parfaitement fonctionnel. En charge sans souci depuis maintenant 6 mois à 80% de sa puissance nominale. Excellent produit professionnel. Délais, caractéristiques techniques, prix et livraison sans commune mesure avec la concurrence. A recommander ps : Le plus, fabrication française renouant avec les années "glorieuses" de l'industrie électronique française de jadis ...  :-)

63 VA · IP00—