IP23 · ventilated enclosure Three-phase isolation transformer 690 V / 400 V + N in an IP23 ventilated enclosure

Three-phase isolation transformer 690 V / 400 V + N

From industrial 690 V to 400/230 V · vector group Dyn11 · 1 to 100 kVA · made in France

No reviews of this model yet

25 kVA36.1 A per phase on the secondary

  • —
  • —
  • 5-year warranty · wound and tested in Gailhan

Key features

This three-phase isolation transformer steps an industrial 3 × 690 V supply down to 3 × 400 V + N: 400 V between phases and 230 V between each phase and neutral. It supplies standard equipment and auxiliaries — 400 V machines, control systems, lighting, sockets — on sites with 690 V distribution: wind turbines, mines and quarries, tunnels, heavy industry. Vector group Dyn11, electrostatic shield as standard, 1 to 100 kVA in IP00, IP23 or IP54, and 125 to 1,000 kVA on request: it is wound and tested in our workshop in Gailhan (Gard, southern France).

Site supply3 × 690 Vheavy industry, wind power, mining
TransformerDyn11steps down and isolates
Your equipment3 × 400 V + N400 V between phases · 230 V phase to neutral
3 × 690 V → 3 × 400 V + NThe standard European supply, derived from the site's 690 V distribution.
230 V between phase and neutralFor lighting, sockets and control systems.
Vector group Dyn11Delta primary, star secondary, neutral brought out to terminal 2N.
Galvanic isolationYour 400 V equipment is electrically separated from the 690 V system.
Electrostatic shield as standardConnected to earth, it limits the transfer of disturbances between primary and secondary.
Made and tested in GailhanWound, wired and 100 % tested in our workshop in the Gard, southern France, before dispatch.
On the 690 V side, equipment rated for 690 V

The feeder supplying the transformer (cables, circuit breaker, isolator) must be rated for 690 V: check its rated operational voltage.

230 V for auxiliaries

Between each phase and the secondary neutral you have 230 V: site lighting, sockets and control systems without another transformer.

Higher insulation level on the 690 V side

Dielectric tests from the datasheet: 5,000 V · 60 s between primary and frame, 5,500 V · 60 s between primary and secondary.

When should you use a 690 V / 400 V three-phase isolation transformer?

  • Supplying the auxiliaries of a wind turbine (lighting, sockets, control systems) from its 690 V system.
  • Supplying 400/230 V to equipment in mines, quarries or tunnel boring machines with 690 V distribution.
  • Connecting standard 400 V machines in a factory with 690 V distribution.
  • Supplying a 400 V test bench from a 690 V system.

It works at 50 Hz, or at 60 Hz on confirmation. It is not suitable for 400 Hz supplies.

Specifications of the 690 V / 400 V + N three-phase isolation transformer

Values for the selected configuration: 25 kVA · IP23.

Rating25 kVA50 Hz · Dyn11
Primary3 × 690 V Δno neutral
Secondary3 × 400 V YN230 V phase-neutral
ProtectionIP23ventilated enclosure
Primary
Phase-to-phase voltage
3 × 690 V
Connection
Delta (Δ)
Rated line current
20.9 A
Terminals
1U 1V 1W + PE
Secondary
Phase-to-phase voltage
3 × 400 V
Connection
Star with neutral (YN)
Rated line current
36.1 A
Phase-to-neutral voltage
230 V
Terminals
2U 2V 2W 2N + PE
Construction
Type
Dry-type transformer, natural cooling
Core
3 limbs, one coil per phase
Insulation class
H (180 °C)
Electrostatic shield
Fitted as standard, earthed
Standards
EN IEC 61558-1 and EN IEC 61558-2-4
Enclosure
IP rating
IP23, ventilated metal enclosure
Overall dimensions L × W × H
525 × 320 × 550 mm
Weight
131 kg
Mounting
2 feet, holes Ø 12 mm
Ambient temperature
40 °C maximum
Performancedesign values
Full-load efficiency97.3 %
No-load losses163 W
Load losses535 W
Full-load voltage drop2.1 %

Ratings and prices

From 1 to 100 kVA. Above that, on request.

A → recommended rating 25 kVA
RatingPrim. / sec. currentRecommended circuit breakerNo-load / load lossesEfficiencyWeightDimensions (mm)Price ex VATDispatch
1 kVA0.8 / 1.4 AD 2 A12 / 59 W93.4 %12 kg340 × 310 × 350€381.583 days
2 kVA1.7 / 2.9 AD 2 A22 / 105 W94.0 %20 kg340 × 310 × 350€430.753 days
2.5 kVA2.1 / 3.6 AD 4 A24 / 125 W94.4 %22 kg340 × 310 × 350€448.253 days
3.15 kVA2.6 / 4.5 AD 4 A30 / 140 W94.9 %26 kg340 × 310 × 350€467.423 days
4 kVA3.3 / 5.8 AD 4 A42 / 232 W93.6 %40 kg460 × 320 × 500€665.753 days
5 kVA4.2 / 7.2 AD 6 A51 / 264 W94.1 %46 kg460 × 320 × 500€694.923 days
6.3 kVA5.3 / 9.1 AD 6 A59 / 289 W94.8 %52 kg460 × 320 × 500€736.583 days
8 kVA6.7 / 11.5 AD 10 A90 / 277 W95.6 %74 kg525 × 335 × 550€1,031.583 days
10 kVA8.4 / 14.4 AD 10 A98 / 325 W95.9 %81 kg525 × 335 × 550€1,094.923 days
12 kVA10.0 / 17.3 AD 16 A114 / 357 W96.2 %92 kg525 × 335 × 550€1,425.753 days
16 kVA13.4 / 23.1 AD 16 A131 / 421 W96.7 %105 kg525 × 335 × 550€1,432.423 days
20 kVA16.7 / 28.9 AD 20 A147 / 513 W96.8 %116 kg525 × 335 × 550€1,514.923 days
25 kVA20.9 / 36.1 AD 25 A163 / 542 W97.3 %131 kg525 × 335 × 550€1,686.583 days
30 kVA25.1 / 43.3 AD 32 A179 / 663 W97.3 %142 kg525 × 335 × 550€1,854.083 days
40 kVA33.5 / 57.7 AD 40 A150 / 867 W97.5 %132 kg700 × 480 × 720€2,255.753 days
50 kVA41.8 / 72.2 AD 50 A206 / 866 W97.9 %173 kg700 × 480 × 720€2,383.253 days
63 kVA52.7 / 90.9 AD 63 A—*—*220 kg700 × 480 × 720€3,789.926 days
80 kVA66.9 / 115.5 AD 80 A—*—*300 kg700 × 480 × 720€4,591.586 days
100 kVA83.7 / 144.3 AD 100 A—*—*345 kg700 × 480 × 720€5,358.256 days
125 to 1,000 kVA
On request, in the standard ratings: 125, 160, 200, 250, 315, 400, 500, 630, 800 and 1,000 kVA. Request a quote

Rated currents: primary at 690 V / secondary at 400 V. Type D circuit breaker on the primary. Losses and efficiency: design values at full load. * 63 to 100 kVA: losses and efficiency on request. Prices exclude carriage. Calculator formula: kVA = √3 × 400 V × A ÷ 1,000 (current on the 400 V side), next standard rating up.

Wiring diagram and enclosure drawing

Extracts from the datasheet: coil-by-coil connections and enclosure dimensions.

Wiring diagram
PRIMARY · DELTA (Δ)U1U21U11UV1V21V11VW1W21W11W
COIL UCOIL VCOIL Wstart1U1end1U2start1V1end1V2start1W1end1W21U1V1W
SECONDARY · STAR WITH NEUTRAL (YN)U2U22U12UV2V22V12VW2W22W12W2N
COIL UCOIL VCOIL WNEUTRALstart2U1end2U2start2V1end2V2start2W1end2W2neutral2N2U2V2W2N
Enclosure IP23 · 25 kVA
ADGA1EBB1CØFØH
Technical document for the TTI690400N series
PDF · specifications, ratings and part numbers, protection
FRENDEESIT

Installation and protection

Values for 25 kVA. Sizing of the installation remains the installer's responsibility.

Upstream protection

Type D circuit breaker 40 A

or aM fuses 40 A · inrush current ≈ 433 A peak

Secondary neutral

  • Earthed: TN-S system, the most common.
  • Isolated from earth: IT system, with an insulation monitoring device.

Safety

  • Connection by a qualified person.
  • Earth connected before switching on.
  • IP00: in a cabinet or a closed electrical room.

Standards, warranty and options

A standard transformer, built to order and adaptable to your installation.

EN IEC 61558-2-4isolating transformers, with Part 1; above 40 kVA, by agreement
CE markingLow Voltage, EMC
RoHSfree of lead and restricted substances
5-year warrantyon our three-phase transformers
Made in FranceGailhan workshop (Gard, southern France)
Fast dispatch3 to 6 working days
Tappings±2.5 %, ±5 % or ±10 %
Other voltagesup to 1,000 V phase-to-phase
60 Hzon confirmation
Other vector groupsDd0, Yyn0, YNyn0, Yd11, YNd11
Temperature sensorsbimetallic, PTC or PT100
Forced ventilation230 V fans
Isolator switchhandle-operated, primary side
Castorsfor large enclosures

Frequently asked questions

About the 690 V / 400 V + N three-phase isolation transformer.

How does it differ from a 400 V / 690 V transformer?

The direction: this three-phase isolation transformer steps a 690 V supply down to 400 V + N. To supply 690 V equipment from a 400 V supply, choose the 400 V → 690 V + N model.

Does the secondary provide 230 V?

Yes: the 690 V to 400 V transformer provides 230 V between each phase and neutral, and 400 V between phases. Connected to earth, the neutral gives a TN-S system.

How do I wire a 690 V / 400 V three-phase isolation transformer?

Primary connection: the supply goes to terminals 1U, 1V and 1W, earth to PE; the delta connection is made at the factory. On the secondary, the outgoing circuits leave from terminals 2U, 2V and 2W, and the neutral from terminal 2N. The full wiring diagram is on the datasheet.

Which rating should I choose?

To choose your 690 V / 400 V three-phase isolation transformer, multiply the current per phase on the 400 V side by 400 V and by √3, then take the next standard rating up. For 32 A per phase: 22.2 kVA, so a 25 kVA unit. The calculator above the table does this for you.

Do you make three-phase transformers above 100 kVA?

Yes, on request: we also make this 690 V / 400 V three-phase isolation transformer from 125 to 1,000 kVA, in the standard ratings 125, 160, 200, 250, 315, 400, 500, 630, 800 and 1,000 kVA. Choose the rating at the top of the page, below the priced ratings, or request a quote: reply within 48 h.

What upstream protection should I install?

On the primary (690 V) of your 690 V / 400 V three-phase isolation transformer, a type D circuit breaker or aM fuses rated for 690 V, sized for the rated current: for 25 kVA, 20.9 A per phase, i.e. a 25 A type D circuit breaker or 25 A aM fuses. At switch-on, the inrush current reaches about twelve times the rated current; the rating for each size is given in the table.

IP00, IP23 or IP54: which should I choose?

IP00: open-frame transformer, to be installed in a cabinet or a closed electrical room. IP23: ventilated enclosure, for a plant room sheltered from water. IP54: closed enclosure, protected against dust and splashing water.

What are the lead times?

From 1 to 50 kVA, dispatched from our workshop within 3 working days; from 63 to 100 kVA, within 6 working days. Up to 30 kg, the transformer ships as a parcel, with free delivery within France. Heavier units travel on a pallet with Kuehne + Nagel: 48 to 72 hours in mainland France, 96 hours elsewhere in Europe; pallet delivery is free from €1,000 ex VAT, otherwise a flat €50 ex VAT.

Customer reviews

No reviews of this model yet. Here is what customers say about another three-phase transformer built the same way (reviews in French).

Julien Moretti · 2 octobre 2025 · sur le 400 V / 400 V + N

Livraison rapide, produit conforme et bien emballé. Installation sans difficulté, parfait pour créer un neutre. Le service téléphonique est top, fabrication française en plus. Je recommande sans hésiter.

Martin Delmas · 21 septembre 2025 · sur le 400 V / 400 V + N

Produit reçu rapidement, très bien emballé. Fonctionne parfaitement sur notre installation industrielle. Fabrication sérieuse, rien à signaler après plusieurs semaines d'utilisation. Content d'acheter français.

Mickaël Dupuy · 3 juin 2025 · sur le 400 V / 400 V + N

Produit conforme à la description, fabrication robuste et délai respecté. Service client à l’écoute, installation réalisée sans souci. Très satisfait de la qualité, matériel professionnel, rien à dire de plus.

25 kVA · IP23—