IP23 · ventilated enclosure Three-phase transformer 400 V / 208 V + N in an IP23 ventilated enclosure

Three-phase transformer 400 V / 208 V + N (208Y/120 V)

North American 208Y/120 V supply in Europe · vector group Dyn11 · 1 to 100 kVA · made in France

No reviews of this model yet

20 kVA55.5 A per phase on the secondary

  • —
  • —
  • 5-year warranty · wound and tested in Gailhan

Key features

This three-phase transformer recreates the North American 208Y/120 V system in Europe: from your 3 × 400 V three-phase supply, it provides 208 V between phases and 120 V between each phase and neutral. It is the solution for running machines built for the United States or Canada — machine tools, commercial kitchen equipment, air conditioning, UPS systems and IT racks. Vector group Dyn11, electrostatic shield as standard, 1 to 100 kVA in IP00, IP23 or IP54, and 125 to 1,000 kVA on request: it is wound and tested in our workshop in Gailhan (Gard, southern France).

Your supply3 × 400 VEuropean mains, 50 Hz
TransformerDyn11steps down and isolates
Your American machine208Y/120 V208 V between phases · 120 V phase to neutral
208 V between phasesThe three-phase voltage of North American commercial buildings.
120 V between phase and neutralFor single-phase circuits and the machine controls.
Vector group Dyn11Delta primary, star secondary, neutral brought out to terminal 2N.
Galvanic isolationYour machine is electrically separated from the European supply that feeds it.
Electrostatic shield as standardConnected to earth, it limits the transfer of disturbances between primary and secondary.
Made and tested in GailhanWound, wired and 100 % tested in our workshop in the Gard, southern France, before dispatch.
The frequency stays at 50 Hz

A three-phase transformer changes the voltage, not the frequency. Check the rating plate of your machine to make sure it accepts 50 Hz (marked “50/60 Hz”): a motor designed for 60 Hz runs about 17 % slower at 50 Hz.

Machine rated 230 or 240 V between phases?

Some North American machines are designed for 230–240 V between phases, not 208 V: in that case you need the 400 V → 230 V + N model. The voltage is shown on the rating plate.

120 V is available

Between each phase and the secondary neutral you have 120 V: the voltage of North American sockets and controls.

When should you use a 400 V / 208 V three-phase transformer?

  • Machine tools and CNC controls imported from the United States or Canada.
  • Commercial kitchens: ovens, fryers and dishwashers designed for 208 V.
  • 208 V air conditioning, chillers and compressors, including rooftop units.
  • UPS systems, PDUs and IT racks designed for the North American supply.
  • Lifts, hoists and drives of North American origin, exhibition or demonstration equipment.

It works at 50 Hz, or at 60 Hz on confirmation. It is not suitable for 400 Hz supplies.

Specifications of the 400 V / 208 V + N three-phase transformer

Values for the selected configuration: 20 kVA · IP23.

Rating20 kVA50 Hz · Dyn11
Primary3 × 400 V Δno neutral
Secondary3 × 208 V YN120 V phase-neutral
ProtectionIP23ventilated enclosure
Primary
Phase-to-phase voltage
3 × 400 V
Connection
Delta (Δ)
Rated line current
28.9 A
Terminals
1U 1V 1W + PE
Secondary
Phase-to-phase voltage
3 × 208 V
Connection
Star with neutral (YN)
Rated line current
55.5 A
Phase-to-neutral voltage
120 V
Terminals
2U 2V 2W 2N + PE
Construction
Type
Dry-type transformer, natural cooling
Core
3 limbs, one coil per phase
Insulation class
H (180 °C)
Electrostatic shield
Fitted as standard, earthed
Standards
EN IEC 61558-1 and EN IEC 61558-2-4
Enclosure
IP rating
IP23, ventilated metal enclosure
Overall dimensions L × W × H
525 × 320 × 550 mm
Weight
131 kg
Mounting
2 feet, holes Ø 12 mm
Ambient temperature
40 °C maximum
Performancedesign values
Full-load efficiency97.3 %
No-load losses163 W
Load losses535 W
Full-load voltage drop2.1 %

Ratings and prices

From 1 to 100 kVA. Above that, on request.

A → recommended rating 25 kVA
RatingPrim. / sec. currentRecommended circuit breakerNo-load / load lossesEfficiencyWeightDimensions (mm)Price ex VATDispatch
1 kVA1.4 / 2.8 AD 2 A12 / 59 W93.4 %12 kg340 × 310 × 350€381.583 days
2 kVA2.9 / 5.6 AD 4 A22 / 107 W94.0 %20 kg340 × 310 × 350€430.753 days
2.5 kVA3.6 / 6.9 AD 4 A24 / 126 W94.3 %22 kg340 × 310 × 350€448.253 days
3.15 kVA4.5 / 8.7 AD 6 A30 / 136 W95.0 %26 kg340 × 310 × 350€467.423 days
4 kVA5.8 / 11.1 AD 10 A42 / 239 W93.4 %40 kg460 × 320 × 500€665.753 days
5 kVA7.2 / 13.9 AD 10 A51 / 255 W94.2 %46 kg460 × 320 × 500€694.923 days
6.3 kVA9.1 / 17.5 AD 10 A59 / 287 W94.8 %52 kg460 × 320 × 500€736.583 days
8 kVA11.5 / 22.2 AD 16 A90 / 284 W95.5 %74 kg525 × 335 × 550€1,031.583 days
10 kVA14.4 / 27.8 AD 16 A98 / 332 W95.9 %81 kg525 × 335 × 550€1,094.923 days
12.5 kVA18.0 / 34.7 AD 20 A—*—*94 kg525 × 335 × 550€1,118.253 days
16 kVA23.1 / 44.4 AD 25 A131 / 407 W96.7 %105 kg525 × 335 × 550€1,432.423 days
20 kVA28.9 / 55.5 AD 32 A147 / 496 W96.9 %117 kg525 × 335 × 550€1,514.923 days
30 kVA43.3 / 83.3 AD 50 A179 / 667 W97.3 %142 kg525 × 335 × 550€1,854.083 days
40 kVA57.7 / 111.0 AD 63 A166 / 771 W97.7 %144 kg700 × 480 × 720€2,255.753 days
50 kVA72.2 / 138.8 AD 80 A190 / 980 W97.7 %161 kg700 × 480 × 720€2,383.253 days
63 kVA90.9 / 174.9 AD 100 A—*—*220 kg700 × 480 × 720€3,789.926 days
80 kVA115.5 / 222.1 AD 125 A—*—*300 kg700 × 480 × 720€4,591.586 days
100 kVA144.3 / 277.6 AMCCB 160 A—*—*345 kg700 × 480 × 720€5,358.256 days
125 to 1,000 kVA
On request, in the standard ratings: 125, 160, 200, 250, 315, 400, 500, 630, 800 and 1,000 kVA. Request a quote

Rated currents: primary at 400 V / secondary at 208 V. Type D circuit breaker on the primary. Losses and efficiency: design values at full load. * 63 to 100 kVA: losses and efficiency on request. Prices exclude carriage. Calculator formula: kVA = √3 × 208 V × A ÷ 1,000 (current on the 208 V side), next standard rating up.

Wiring diagram and enclosure drawing

Extracts from the datasheet: coil-by-coil connections and enclosure dimensions.

Wiring diagram
PRIMARY · DELTA (Δ)U1U21U11UV1V21V11VW1W21W11W
COIL UCOIL VCOIL Wstart1U1end1U2start1V1end1V2start1W1end1W21U1V1W
SECONDARY · STAR WITH NEUTRAL (YN)U2U22U12UV2V22V12VW2W22W12W2N
COIL UCOIL VCOIL WNEUTRALstart2U1end2U2start2V1end2V2start2W1end2W2neutral2N2U2V2W2N
Enclosure IP23 · 25 kVA
ADGA1EBB1CØFØH
Technical document for the TTI400208N series
PDF · specifications, ratings and part numbers, protection
FRENDEESIT

Installation and protection

Values for 25 kVA. Sizing of the installation remains the installer's responsibility.

Upstream protection

Type D circuit breaker 40 A

or aM fuses 40 A · inrush current ≈ 433 A peak

Secondary neutral

  • Earthed: TN-S system, the most common.
  • Isolated from earth: IT system, with an insulation monitoring device.

Safety

  • Connection by a qualified person.
  • Earth connected before switching on.
  • IP00: in a cabinet or a closed electrical room.

Standards, warranty and options

A standard transformer, built to order and adaptable to your installation.

EN IEC 61558-2-4isolating transformers, with Part 1; above 40 kVA, by agreement
CE markingLow Voltage, EMC
RoHSfree of lead and restricted substances
5-year warrantyon our three-phase transformers
Made in FranceGailhan workshop (Gard, southern France)
Fast dispatch3 to 6 working days
Tappings±2.5 %, ±5 % or ±10 %
Other voltagesup to 1,000 V phase-to-phase
60 Hzon confirmation
Other vector groupsDd0, Yyn0, YNyn0, Yd11, YNd11
Temperature sensorsbimetallic, PTC or PT100
Forced ventilation230 V fans
Isolator switchhandle-operated, primary side
Castorsfor large enclosures

Frequently asked questions

About the 400 V / 208 V + N three-phase transformer.

Why 208 V and 120 V?

It is the supply used in North American commercial buildings: 208 V between phases, 120 V between a phase and neutral. This three-phase transformer reproduces it from the European 3 × 400 V supply.

My machine is designed for 60 Hz: is that a problem?

The 400 V to 208 V transformer does not change the frequency: the machine will receive 50 Hz. If its rating plate says “50/60 Hz”, all is well. If not, motors run about 17 % slower and may overheat: ask the machine manufacturer for advice.

208 V or 230/240 V: which should I choose?

Whichever is on the machine rating plate. 208 V: this transformer. 230 or 240 V between phases: the 400 V → 230 V + N model.

How do I wire a 400 V / 208 V three-phase transformer?

Primary connection: the supply goes to terminals 1U, 1V and 1W, earth to PE; the delta connection is made at the factory. On the secondary, the outgoing circuits leave from terminals 2U, 2V and 2W, and the neutral from terminal 2N. The full wiring diagram is on the datasheet.

Which rating should I choose?

To choose your 400 V / 208 V three-phase transformer, multiply the current per phase on the 208 V side by 208 V and by √3, then take the next standard rating up. For 40 A per phase: 14.4 kVA, so a 16 kVA unit. The calculator above the table does this for you.

Do you make three-phase transformers above 100 kVA?

Yes, on request: we also make this 400 V / 208 V three-phase transformer from 125 to 1,000 kVA, in the standard ratings 125, 160, 200, 250, 315, 400, 500, 630, 800 and 1,000 kVA. Choose the rating at the top of the page, below the priced ratings, or request a quote: reply within 48 h.

What upstream protection should I install?

On the primary (400 V) of your 400 V / 208 V three-phase transformer, a type D circuit breaker or aM fuses sized for the rated current: for 20 kVA, 28.9 A per phase, i.e. a 32 A type D circuit breaker or 32 A aM fuses. At switch-on, the inrush current reaches about twelve times the rated current; the rating for each size is given in the table.

IP00, IP23 or IP54: which should I choose?

IP00: open-frame transformer, to be installed in a cabinet or a closed electrical room. IP23: ventilated enclosure, for a plant room sheltered from water. IP54: closed enclosure, protected against dust and splashing water.

What are the lead times?

From 1 to 50 kVA, dispatched from our workshop within 3 working days; from 63 to 100 kVA, within 6 working days. Up to 30 kg, the transformer ships as a parcel, with free delivery within France. Heavier units travel on a pallet with Kuehne + Nagel: 48 to 72 hours in mainland France, 96 hours elsewhere in Europe; pallet delivery is free from €1,000 ex VAT, otherwise a flat €50 ex VAT.

Customer reviews

No reviews of this model yet. Here is what customers say about another three-phase transformer built the same way (reviews in French).

Julien Moretti · 2 octobre 2025 · sur le 400 V / 400 V + N

Livraison rapide, produit conforme et bien emballé. Installation sans difficulté, parfait pour créer un neutre. Le service téléphonique est top, fabrication française en plus. Je recommande sans hésiter.

Martin Delmas · 21 septembre 2025 · sur le 400 V / 400 V + N

Produit reçu rapidement, très bien emballé. Fonctionne parfaitement sur notre installation industrielle. Fabrication sérieuse, rien à signaler après plusieurs semaines d'utilisation. Content d'acheter français.

Mickaël Dupuy · 3 juin 2025 · sur le 400 V / 400 V + N

Produit conforme à la description, fabrication robuste et délai respecté. Service client à l’écoute, installation réalisée sans souci. Très satisfait de la qualité, matériel professionnel, rien à dire de plus.

20 kVA · IP23—